Search:
|
Return
to Solar Strategies.
City of Aspen/ Pitkin County Energy Conservation
Code
Chapter 8.20 BUILDING CODE
The 1999 Aspen/Pitkin Energy Conservation
Code adopted and incorporated by reference as Appendix Chapter
13, Section 1302.2, to the Uniform Building Code, 1999 Edition,
as codified is amended as follows:
CHAPTER 1 ADMINISTRATION
SECTION 101 - TITLE, PURPOSE,
AND SCOPE
101.1 Title. These regulations
shall be known as the 1999 Aspen/Pitkin Energy Conservation Code,
may be cited as such and will be referred to herein as "this
Code".
101.2 Purpose. The purpose of
this code is to provide minimum standards for the conservation
of energy obtained from depletable sources by regulating and
controlling the design, construction, quality of materials, location
and maintenance of all buildings and structures within this jurisdiction
and certain equipment specifically regulated herein.
101.3 Scope. The provisions of
this code shall apply to all buildings for which an application
for a building permit or renewal of an existing permit is filed
or is required by law to be filed; and, that are either directly
or indirectly conditioned by mechanical heating or mechanical
cooling.
EXCEPTION: Qualified "Historic
Buildings" as defined in Chapter 2, Section 209 of this
Code.
SECTION 107 - FEES
The APECC review and compliance
fee shall be 10% of the associated permit fee. The minimum review
and compliance fee for building permits shall be $20.00.
Exception: Structures that comply with the Aspen
Pitkin Green Program, shall have a 50% reduction in APECC energy
permit fee.
SECTION 108 -- INSPECTIONS
See Section 108 of the 1997 UBC
108.1 Energy Conservation Code
inspections. The Building Division shall inspect new construction
to determine whether it is consistent with approved plans and
specifications, and complies with this code. Certificates of
Occupancy shall not be issued until such consistency is verified.
SECTION 110 - CALCULATION METHODS
AND ALTERNATE COMPONENT PACKAGES
110.1 Public Domain Computer
Program. In addition to the present approved public domain computer
programs, the Chief Building Official may, upon written application
or his/her own motion, approve additional public domain computer
programs that may be used to demonstrate that the proposed building
designs meet the requirements of this code.
The Chief Building Official shall
ensure that user's manuals or guides for each approved program
are available.
SECTION 111 - CERTIFICATION OF
ENERGY PROFESSIONALS
111.1 Certification. Certification
for designers, licensed contractors ·and superintendents
will be available through seminars and testing approved by the
Chief Building Official. As an alternate an E-Star TM rated Design
Professional Certification shall be acceptable.
111.1.1 The design professional
test will deal with designing for compliance and documenting
compliance. Once the design professional has passed the test
he/she will be Certified Energy Design Professional by the Chief
Building Official.
Certified Energy Design Professionals
will be entitled to submit Certified Documentation of Compliance
with a building permit application. Certification will exempt
that application from detailed review except for random audits.
Certification will be revoked
if the design professional shows disregard of the regulations
or if they certify documents that do not comply.
111.1.2 The licensed contractor
or superintendent test will deal with building structures to
maintain compliance. Once the licensed contractor or superintendent
has passed the test he/she will be Certified Energy Building
Professional by the Chief Building Official, as an alternate
an E-Star TM rated Builder shall be acceptable.
Certified Energy Building Professionals
will be entitled to certify compliance for structures they build.
Certification will exempt those structures from detailed inspections
for energy code compliance except for random audits.
Certification will be revoked
if the Certified Energy Building Professionals show disregard
of the regulations or if they certify structures that do not
comply.
CHAPTER 2 DEFINITIONS AND ABBREVIATIONS
SECTION 202 -
A ACCESSIBLE is having access
thereto, but which first may require removal or opening of access
panels, doors, or similar obstructions.
ADDITION is any change to a building
that increases conditioned floor area and/or conditioned volume.
ALTERATION is any change to a
building's water heating system, space conditioning system, or
envelope that is not an addition.
ALTERNATIVE CALCULATION METHODS
(ACMs) are the City of Aspen/Pitkin County Energy Code Public
Domain Computer Programs, one of the City of Aspen/Pitkin County
Energy Code Simplified Calculation Methods, or any other calculation
method approved by the Chief Building Official.
APCDD is the Aspen/Pitkin Community
Development Department.
APPLIANCE EFFICIENCY REGULATIONS
is NAECA.
APPROVED BY THE CHIEF BUILDING
OFFICIAL means approval under Uniform Building Code.
APPROVED CALCULATION METHOD (See
ALTERNATIVE CALCULATION METHODS).
ASPEN PITKIN GREEN PROGRAM is
a guide to the green construction of homes and subdivisions,
compiled by the National Association of Home Builders, ERHC,
as amended and published by the Aspen/Pitkin Community Development
Department Building Division
SECTION 203 - B
SECTION 204 - C
CLIMATE ZONE is the geographic
areas of Pitkin County for which the Aspen/Pitkin Regional Building
Division has jurisdiction.
COMPLIANCE APPROACH means any
one of the allowable methods by which design and construction
of a building may be demonstrated to be in compliance with Chapter
3.
CONDITIONED FLOOR AREA (CFA)
is the floor area (in square feet) of enclosed conditioned space
on all floors of a building, as measured at the floor level of
the exterior surfaces of exterior walls enclosing the conditioned
space.
CONDITIONED SPACE is space in
a building that is either directly conditioned or indirectly
conditioned.
CONDITIONED VOLUME is the total
volume (in cubic feet) of the conditioned space within a building.
COVERED PRODUCT is an appliance
regulated by the efficiency standards established under the National
Appliance Energy Conservation Act (NAECA), 42 U.S.C. Section
6291 of 1987.
CRAWL SPACE is an unfinished
space immediately under the first floor of a building adjacent
to grade less than 5?6? in height.
SECTION 205 - D
DECORATIVE GAS APPLIANCE is a
gas appliance that is designed or installed for visual effect
only, cannot burn solid wood, and simulates a fire in a fireplace.
DEGREE DAY, HEATING is a unit,
based upon temperature difference and time, used in estimating
fuel consumption and specifying nominal annual heating load of
a building. For any one day, when the mean temperature is less
than 65?F, there exist, as many degree days as there are Fahrenheit
degrees difference in temperature between the mean temperature
for the day and 65?F. The number of degree days for use with
this code is 8,850.
DEMISING PARTITIONS AND WALLS
are bafflers that separate conditioned space from enclosed unconditioned
space.
DESIGN CONDITIONS are the parameters
and conditions used to determine the performance requirements
of space conditioning systems. Design conditions for determining
design heating and cooling loads are specified in Section 305.1.7.2.
DESIGN HEAT LOSS RATE is the
total calculated heat loss through the building envelope under
design conditions.
SECTION 206 - E
ENCLOSED SPACE is space that is
substantially surrounded by solid surfaces.
ENERGY BUDGET is the maximum
amount of source energy that a proposed building, or portion
of a building, can be designed to consume, calculated with the
approved procedures specified in Chapter 3.
ENERGY CONSERVATION STANDARDS
means City of Aspen/Pitkin County Energy Conservation Code, Chapter
3.
ENERGY OBTAINED FROM DEPLETABLE
SOURCES is electricity purchased from a public utility, or any
energy obtained from coal, oil, natural gas, or liquefied petroleum
gases.
ENERGY OBTAINED FROM NONDEPLETABLE
SOURCES is energy that is not energy obtained from depletable
sources.
ENFORCING AGENCY is the Aspen/Pitkin
County Community Development Department, Building Division.
ENTIRE BUILDING is the ensemble
of all enclosed space in a building, including the space for
which a permit is sought, plus all existing conditioned and unconditioned
space within the structure.
ENVELOPE means building envelope
ERHC E-STAR TM A program provided
through Energy Rated Homes of Colorado which rates the energy
efficiency of a structure.
EXFILTRATION is uncontrolled
outward air leakage from inside a building, including leakage
through cracks and interstices, around windows and doors, and
through any other exterior partition or duct penetration.
EXISTING BUILDING is a building
constructed prior to the adoption of the Aspen/Pitkin Energy
Conservation Code dated February 12, 1996.
EXPOSED THERMAL MASS is mass
that is directly exposed (uncovered) to the conditioned space
of the building.
EXTERIOR FLOOR/SOFFIT is a horizontal
exterior partition, or a horizontal demising partition, under
conditioned space. For residential occupancies, exterior floors
also include those on grade.
EXTERIOR PARTITION is an opaque,
translucent, or transparent solid baffler that separates conditioned
space from ambient air or space that is not enclosed. For low-rise
residential occupancies, exterior partitions also include bafflers
that separate conditioned space from unconditioned space, or
the ground.
EXTERIOR ROOF/CEILING is an exterior
partition, or a demising partition, that has a slope less than
60 degrees from horizontal, that has conditioned space below,
and that is not an exterior door or skylight.
EXTERIOR ROOF/CEILING AREA is
the area of the exterior surface of exterior roof/ceilings.
EXTERIOR WALL is any wall or
element of a wall, or any member or group of members, which defines
the exterior boundaries or courts of a building and which has
a slope of 60 degrees or greater with the horizontal plane. An
exterior wall or partition is not an exterior floor/soffit, exterior
door, exterior roof/ceiling, window, skylight, or demising wall.
EXTERIOR WALL AREA is the area
of the opaque exterior surface of exterior walls.
SECTION 207 - F
FENESTRATION PRODUCT is any transparent
or translucent material plus any sash, frame, mullions, and dividers,
in the envelope of a building, including, but not limited to:
windows, sliding glass doors, french doors, skylights, curtain
walls, and garden windows.
FIREPLACE is a hearth and fire
chamber or similar prepared place in which a solid fuel fire
may be burned, as defined in UBC Section 3102.2 and as further
clarified in UBC Section 3102.7; these include but are not limited
to factory-built fireplaces, masonry fireplaces, and masonry
heaters (solid fuel burning device).
SECTION 208 - G
GAS HEATING SYSTEM is a natural
gas or liquefied petroleum gas heating system.
GAS LOG is a self-contained,
freestanding, open-flame, gas-burning appliance consisting of
a metal frame or base supporting simulated logs, and designed
for installation only in a vented fireplace.
GLAZING (See FENESTRATION PRODUCT).
GROSS EXTERIOR ROOF AREA is the
sum of the skylight area and the exterior roof ceiling area.
GROSS EXTERIOR WALL AREA is the
sum of the window area, door area, and exterior wall area.
SECTION 209 - H
HABITABLE STORY is a story that
contains space in which humans may work or live in reasonable
comfort, and that has at least 50 percent of its volume above
grade.
HISTORIC BUILDING is a building
or structure that has been designated by official action of the
legally constituted authority of this jurisdiction as having
special historic or architectural significance.
SECTION 210 - I
INDIRECTLY CONDITIONED SPACE
is enclosed space that is not directly conditioned.
INFILTRATION is uncontrolled
inward air leakage from outside a building, or unconditioned
space, including leakage through cracks and interstices, around
windows and doors, and through any other exterior or demising
partition or pipe or duct penetration.
SECTION 213 - L
SECTION 214 - M
MANUFACTURED DEVICE is any heating,
cooling, ventilation, water heating, refrigeration, cooking,
plumbing fitting, insulation, door, fenestration product, or
any other appliance, device, equipment, or system subject to
this code.
MECHANICAL HEATING is raising
the temperature within a space for the purpose of maintaining
human comfort using electric resistance heaters, fossil fuel
burners, heat pumps, or other systems that require energy from
depletable sources.
MEC CHECK is Version 2.07 of
a prescriptive compliance method that was developed by Pacific
Northwest Laboratory (Battelle Memorial Institute) for use with
the 1995 MEC.
MODELING ASSUMPTIONS are the
conditions (such as weather conditions, thermostat settings and
schedules, internal gain schedules, etc.) that are used for calculating
a building's annual energy consumption and that are in the Alternative
Calculation Methods Manuals.
MODEL ENERGY CODE is the 1995
Model Energy Code prepared by the Council of American Building
Officials.
SECTION 215 - N
NAECA is the National Appliance
Energy Conservation Act of 1987 (Public Law 100-12).
NATIONAL FENESTRATION RATING
COUNCIL is the NFRC, certified products directory, published
by NFRC, incorporated, 1300 Spring Street, Suite 120, Silver
Spring, Maryland, 20910.
NON-VENTED ROOF/CEILING ASSEMBLY
as referenced in this code is an assembly that complies with
the policy adopted by the Building Division for the control of
moisture in the interior insulation of the roof and has been
approved by the building official
SECTION 216 - O
OPERABLE SHADING DEVICE is a
device at the interior or exterior of a building or integral
with a fenestration product, which is capable of being operated,
either manually or automatically, to adjust the amount of solar
radiation admitted to the interior of the building.
OPTIMAL OVERHANG is an overhang
that completely shades the glazing at solar noon on August 21
and substantially exposes the glass at solar noon on December
21.
SECTION 217 - P
SECTION 219 - R
RP is the responsible person.
RAISED FLOOR is a floor partition)
over a crawl space, or an unconditioned space, or ambient air.
READILY ACCESSIBLE is capable
of being reached quickly for operation, repair, or inspection,
without requiring climbing or removing obstacles, or resorting
to access equipment.
RELATIVE SOLAR HEAT GAIN is the
ratio of solar heat gain through a fenestration product (corrected
for external shading) to the solar heat gain from an unshaded
single light of 1/8 inch thick clear double strength glass under
the same set of conditions, excluding the effects of mullions,
frames and sashes.
RENEWABLE ENERGY MITIGATION PROGRAM
is designed to offset the environmental impacts and greenhouse
gas emissions produced by non-complying exterior snowmelt, pool,
and spa systems and by homes exceeding 5,000 square feet. Fees
collected by the program will be used to fund energy efficiency
and renewable energy installations in the City of Aspen and Pitkin
County and, if necessary, purchase wind energy from wind generators
in Colorado or Wyoming. It will be administered by the Board
of Directors of the Community Office for Resource Efficiency
(CORE).
REPAIR is the reconstruction
or renewal of any part of an existing building for the purpose
of its maintenance.
REPAIR OR REPLACEMENT GLAZING
is glazing without a frame, associated with a repair that is
not an addition or alteration.
RESIDENTIAL BUILDING is a building
that is of occupancy group R-1, R-2, R-3, or R-4 or U-1 (associated
with a group R).
RESPONSIBLE PERSON (RP) (See
Section 106.3.6 Responsibility for Signing).
SECTION 220 - S
SERVICE SNOWMELT HEATER is an
appliance designed to heat a liquid for the purpose of melting
ice and snow.
SERVICE WATER HEATER is an appliance
designed primarily to supply hot water for sanitary purposes
for human occupancy, other than for comfort heating.
SERVICE WATER HEATING is heating
of water for sanitary purposes for human occupancy, other than
for comfort heating.
SHADING COEFFICIENT (SC) is the
ratio of the solar heat gain through a fenestration product to
the solar heat gain through an unshaded 1/8 inch thick clear
double strength glass under the same set of conditions. For nonresidential,
high-rise residential, and hotel/motel buildings, this shall
exclude the effects of mullions, frames, sashes, and interior
and exterior shading devices.
SITE BUILT WINDOWS are those
products which are field constructed from elements, including
framing, glazing, weather-stripping, not sold together as a fenestration
product.
SITE SOLAR ENERGY is natural
daylighting, or thermal, chemical, or electrical energy derived
from direct conversion of incident solar radiation at the building
site.
SKYLIGHT is glazing having a
slope less than 60 degrees from the horizontal with conditioned
space below.
SKYLIGHT AREA is the area of
the surface of a skylight, plus the area of the frame, sash,
and mullions.
SNOWMELT is the mechanical melting
of snow on driveways, walkways, etc.
SOLID FUEL BURNING DEVICE shall
mean a burning device designed for solid fuel combustion so that
usable heat is derived for the interior of a building, and includes,
without limitation, solid fuel-fired stoves, wood stoves or any
nature, fireplaces, pellet stoves, solid fuel-fired cooking stoves,
combination fuel furnaces or boilers which bum solid fuel, or
any other device used for the burning of solid combustible material.
Solid fuel burning devices do not include gas log fireplaces,
decorative gas appliances or electrical appliances.
SOURCE ENERGY is the energy that
is used at a site and consumed in producing and in delivering
energy to a site, including, but not limited to, power generation,
transmission, and distribution losses, and that is used to perform
a specific function, such as space conditioning, lighting or
water heating. Table 3-1 contains the conversion factors for
converting site to source energy.
SPA is a unit primarily designed
for therapeutic use which is not drained, cleaned or refilled
for each individual. It may include, but not limited to, hydrojet
circulation, hot water, cold water, mineral baths, air induction
bubbles, or any combination thereof. Industry terminology for
spa includes, but is not limited to, therapeutic pool, hydrotherapy
pool, whirlpool, hot spa, etc.
SPA POOL-PRIVATE is a pool, not
under medical supervision, that incorporates water jets and/or
an aeration system used for hydro massage in connection with
a single family residence, and available only to family of the
householder and his private guests.
SPA POOL-PUBLIC is a pool, not
under medical supervision, that incorporates water jets and/or
an aeration system used for hydro massage.
SPACE CONDITIONING SYSTEM is
a system that provides either collectively or individually heating,
ventilating, or cooling within or associated with conditioned
spaces in a building.
SWIMMING POOL is any constructed
or prefabricated pool used for swimming or bathing, twenty-four
(24) inches or more in depth.
SWIMMING POOL-PRIVATE is all
constructed pools which are used as a swimming pool in connection
with a single family residence, and available only to family
of the householder and his private guests.
SWIMMING POOL-PUBLIC is any constructed
pool other than a private swimming pool.
SYSTEM is a combination of equipment,
controls, accessories, interconnecting means, or terminal elements,
by which energy is transformed to perform a specific function,
such as space conditioning, or service water heating.
SECTION 221 - T
THERMAL MASS is solid or liquid
material used to store heat for later heating use or for reducing
cooling requirements.
THERMAL RESISTANCE (R) is the
resistance of a material or building component to the passage
of heat in (hr x ft 2 x OF)/Btu.
SECTION 222 - U
UBC is the 1997 edition of the
Uniform Building Code.
UMC is the 1997 edition of the
Uniform Mechanical Code.
UNCONDITIONED SPACE is enclosed
space within a building that is not conditioned space.
U-VALUE is the overall coefficient
of thermal transmittance of a construction assembly, in Btu/(hr
x ft 2 x OF), including air film resistance at both surfaces.
SECTION 223 - V
SECTION 224 - W
WATER STORAGE TANK is an unfired
or indirectly heated water tank used for storage of hot water.
WINDOW is glazing that is not
a skylight.
WINDOW AREA is the area of the
surface of a window, plus the area of the frame, sash, and mullions.
WINDOW WALL RATIO is the ratio
of the window area to the gross exterior wall area.
WOOD HEATER is an enclosed wood
burning appliance used for space heating and/or domestic water
heating, and which meets the requirements of the Aspen/Pitkin
Environmental Health Department.
WOOD STOVE (See WOOD HEATER).
SECTION 227 - Z
CHAPTER 3
ENERGY CONSERVATION STANDARDS
SECTION 301 - ALL OCCUPANCIES
- GENERAL PROVISIONS
301.1 Buildings covered. The
provisions of Chapter 3 apply to all buildings (see Section 101.3)
and to all snowmelt, private swimming pool and spa heating system
equipment (see Section 101.3.1).
301.2 Parts of Buildings Covered.
The provisions of Chapter 3 apply to the building envelope, space
conditioning systems, water heating systems, snowmelt systems,
and private pool and spa heating systems of buildings covered
by this code.
EXCEPTIONS:
1. Packaged portable spas =<
64sq. ft. of surface water area listed by a nationally recognized
testing laboratory with a minimum R12 cover.
2. Areas critical to pedestrian
ingress, egress, or life safety may be snowmelted, with approval
from the Chief Building Official, on a case by case basis.
301.3 Floors and Habitable Stories.
1. Only habitable floors that
have at least 50 percent of their volume above grade as defined
in the UBC shall be counted in determining how many habitable
stories a building has.
2. All conditioned space in a
floor shall comply with this code, whether or not the floor is
above grade and whether or not it is habitable.
301.4 Mixed Occupancy. When a
building is designed and constructed for more than one type of
occupancy, the space for each occupancy shall meet the provisions
of this code applicable to that occupancy.
EXCEPTION: If one occupancy constitutes
at least 90 percent of the conditioned floor area of the building,
the entire building may comply with the provisions of this code
applicable to that occupancy.
301.5 Certification Requirements
for Manufactured Devices. This code limits the installation of
the following manufactured devices to those that have been certified
by their manufacturer to meet or exceed minimum specifications
or efficiencies adopted by the Chief Building Official:
1. Central air-conditioning heat
pumps and other central air conditioners. 2. Combination equipment:
space heating and cooling, or space heating and water heating.
3. Fenestration products. 4. Gas space heaters. 5. Insulating
materials. 6. Oil fired storage water heaters. 7. Other heating
and cooling equipment. 8. Plumbing fixtures. 9. Pool heaters.
10. Refrigerators, refrigerator-freezers, and freezers. 11. Room
air conditioners. 12. Slab floor perimeter insulation. 13. Snowmelt
Boilers. 14. Solid fuel burning devices. 15. Water heaters.
301.5.1 The certification status
of any such manufactured device may be confirmed only by reference
to:
1. A directory published or approved
by the Chief Building Official; or 2. A copy of the application
for certification from the manufacturer and the letter of acceptance
from the Building Division staff; or 3. Written confirmation
from the publisher of a division-approved directory that a device
has been certified; or 4. A division-approved label on the device;
or 5. The National Appliance Energy Conservation Act of 1987.
6. The National Fenestration Rating Council.
NOTE: Section 301.5 does not
require a builder, designer, owner, operator, or enforcing agency
to test any certified device to determine its compliance with
minimum specifications or efficiencies adopted by the Chief Building
Official.
SECTION 302 - CALCULATION OF SOURCE
ENERGY CONSUMPTION.
When calculating source energy
consumption, consumption of electricity, natural gas, fuel oil,
and LPG shall be converted to BTUs at the rates shown in Table
3-1.
Table 3-1
Source Energy Conversion Rates
Energy Source BTU per unit Consumption
Electricity 10.239 BTU/kilowatt-hour Natural Gas 100,000 BTU/therm/100
at 14.73 psia Fuel Oil 138,400 BTU/gallon LPG 91,080 BTU/gallon
SECTION 303 - MANDATORY REQUIREMENTS
FOR SERVICE SNOWMELT SYSTEM AND EQUIPMENT.
303.1 Any service snowmelt system
or equipment shall meet the following:
EXCEPTIONS:
1. Roof Heating Cable. 2. Areas
critical to pedestrian ingress, egress, or life safety may be
snowmelted, with approval from the Chief Building Official, on
a case by case basis.
303.2 Snowmelt systems shall
include automatic temperature and surface moisture controls.
EXCEPTIONS:
1. Roof Heating Cable. 2. Areas
critical to pedestrian ingress, egress, or life safety may be
snowmelted, with approval from the Chief Building Official, on
a case by case basis.
SECTION 304 - MANDATORY REQUIREMENTS
FOR SOLID FUEL BURNING DEVICES.
SECTION 305 - RESIDENTIAL MANDATORY
FEATURES AND DEVICES Any new residential building shall meet the
requirements of this Section.
305.1 Ceilings. The opaque portions
of ceilings separating conditioned spaces from unconditioned
spaces or ambient air shall meet the requirements of either 1
or 2 below:
1. Ceilings shall be insulated
between wood framing members with insulation resulting in an
installed thermal resistance of R-30 or greater for the insulation
alone.
ALTERNATIVE: Insulation which
is not penetrated by framing members may meet an R-value equivalent
to installing R-30 insulation between wood framing members and
accounting for the thermal effects of framing members.
2. The weighted average U-value
of ceilings shall not exceed the U-value that would result from
installing R-30 insulation between wood framing members in the
entire ceiling and accounting for the effects of framing members.
When loose fill insulation is
installed, the minimum installed weight per square foot shall
conform with the insulation manufacturer's installed design weight
per square foot at the manufacturer's labeled R-value.
305.2 Walls. The opaque portions
of frame walls separating conditioned spaces from unconditioned
spaces or ambient air shall meet the requirements of either 1
or 2 below:
1. Framed walls shall be insulated
between framing members with insulation having a thermal resistance
of R-19. Framed foundation walls of heated basements or heated
crawl spaces shall be insulated above the adjacent outside ground
line with insulation having a thermal resistance of at least
R-19.
ALTERNATIVE: Insulation which
is not penetrated by framing members may meet an R-value equivalent
to installing R-19 insulation between wood framing members and
accounting for the thermal effects of framing members.
2. The weighted average U-value
of walls shall not exceed the U-value that would result from
installing R-19 insulation between wood framing members and accounting
for the effects of framing members.
305.3 Floors. Concrete raised
floors over unconditioned space shall be insulated to an installed
thermal resistance of at least R-19. All other raised floors
separating conditioned space from unconditioned space shall meet
the requirements of either 1 or 2 below:
1. Floors shall be insulated
between wood framing members with insulation having an installed
thermal resistance of R-19 or greater.
2. The weighted average U-value
of other floor assemblies shall not exceed the U-value that would
result from installing R-19 insulation between wood framing members
and accounting for the effects of framing members.
ALTERNATIVE: Raised floor insulation
may be omitted if the foundation walls are insulated to an installed
thermal resistance of R-19, and a vapor barrier is placed over
the entire floor of the crawl space, and a mechanical ventilation
system that meets the requirements of UBC Section 2317.7 is installed.
305.4 Installation of Fireplaces,
Decorative Gas Appliances, and Gas Logs.
305.4.1 Wood burning fireplaces
are prohibited in non-attainment areas of the City of Aspen and
Pitkin County.
305.4.2 If a masonry or factory
built wood burning fireplace is installed, it shall have the
following:
1. CLOSEABLE metal or glass doors
covering the entire opening of the firebox; 2. A combustion air
intake to draw air from the outside of the building directly into
the fire box, which is at least 6-square inches in area; and 3.
A flue damper with a readily accessible control.
EXCEPTION: When a gas log, log
lighter, or decorative gas appliance is installed in a fireplace,
the flue damper shall be blocked open as required by the manufacturer's
installation instructions or Section 803 1997 UMC.
305.4.3 If a gas log or gas insert
is installed in an existing masonry fireplace, it shall have the
following:
1. CLOSEABLE metal or glass doors
covering the entire opening of the firebox. 2. Flue damper permanently
block open per 1997 UMC Section 901.2 3. A combustion air intake
to draw air from the outside of the building directly into the
fire box, which is at least 6-square inches in are
A 305.5. Infiltration Barrier.
If an infiltration baffler is installed to meet the requirements
of Sections 306 and 307, it must have an air porosity of less
than 5 cubic feet per hour per square foot per inch of mercury
pressure difference when tested in accordance with the requirements
of ASTM E-283-84. If a vapor barrier functions as an infiltration
barrier it shall be located on the conditioned side of the exterior
framing.
305.6 Vapor Retarders. A vapor
retarder shall be installed on the conditioned space side of all
insulation in all exterior walls and ceilings to protect insulation
from condensation. Penetrations of vapor barriers shall be sealed
at the edge of the penetration. Recessed lights that penetrate
vapor barriers shall be "air tight".
EXCEPTIONS: Vapor retarders shall
not be installed:
1. On approved non-vented insulated
roof ceiling assemblies. See Section 215. 2. On below grade walls
305.7 Space Conditioning Equipment.
305.7.1 Building design heat loss
rate and design heat gain rate, shall be determined using a method
based on any one of the following:
1. The American Society of Heating,
Refrigeration, and Air-conditioning Engineers (ASHRAE) Handbook
and Product Directory, Equipment Volume (1988), Systems and Applications
Volume (1987), and Fundamentals Volume (1989), or 2. The Sheet
Metal Air Conditioning Contractors National Association (SMACNA)
Load Calculation Manual, or 3. The Air Conditioning Contractors
of America (ACCA) Manual J.
The design heat loss rate and
design heat gain rate, are two of the criteria that shall be used
for equipment sizing and selection.
NOTE: Heating Systems must meet
the minimum heating capacity required by UBC Section 310.11. The
furnace output capacity and other specifications are published
in the Building Department's directory of certified equipment
or other directories approved by the Chief Building Official.
3.05.7.2 Design Conditions. For
the purpose of sizing the space conditioning (HVAC) system, the
indoor design temperatures shall be 70 degrees Fahrenheit for
heating and 75 degrees Fahrenheit for cooling. The outdoor heating
design temperature shall be 15ºF. The outdoor cooling design
dry bulb temperature shall be 81ºF. The outdoor cooling design
wet bulb temperature shall be 59ºF.
305.8 Setback Thermostats. All
heating and/or cooling systems other than solid fuel burning devices
shall have an automatic thermostat with a clock mechanism or other
setback mechanism approved by the Chief Building Official that
shuts the system off during periods of non-use and that allows
the building occupant to automatically set back the thermostat
set points for at least 2 periods within 24 hours.
EXCEPTION: Gravity gas wall heaters,
gravity floor heaters, gravity room heaters, room air conditioners,
and room air conditioner heat pumps need not comply with this
requirement. Additionally, room air conditioner heat pumps need
not comply with Section 305.8.
305.9 Pipe and Tank Systems.
305.9.1 Hot water tanks shall
be externally wrapped with insulation having an installed thermal
resistance of R-12 or greater or have internal insulation of at
least R-16 and a label on the exterior of the tank showing the
insulation R-value.
305.9.2 The piping for all space
conditioning and service water heating systems, in unconditioned
spaces; and, the first five feet of hot and cold water pipes from
the storage tanks of non-recirculating systems shall be insulated
in accordance with Table 3-2.
Table 3-2
Pipe Insulation Requirements Minimum
R-Value
System Pipe Diameter
Less than or equal to 2"
Greater than 2" Domestic Hot Water R-4 R-6 Hydronic Heating
Supply Lines R-4 R-6 Cooling Systems (pipes below 55?) R-3 R-4
EXCEPTION: The following piping
does not have to be thermally insulated:
1. Factory-installed piping within
space conditioning equipment 2. Piping that conveys fluids that
have a design operating temperature range between 55 degrees and
105 degrees Fahrenheit. 3. Gas piping, cold domestic water piping,
condensate drains, vents, or waste piping. 4. Where the heat gain
of heat loss to or from piping without insulation will not increase
building source energy use.
NOTE: Where the Chief Building
Official approves a water heater calculation method for a particular
water heating recirculation system, piping insulation requirements
shall be those specified in the approved calculation method.
305.10 Slab Edge Insulation. Concrete
slab edges shall be insulated to an installed thermal resistance
of at least R-l 0. Material used for slab edge insulation shall
meet the following minimum specifications:
1. Water absorption rate no greater
than 0.3 percent when tested in accordance with ASTM-C-271. 2.
Water vapor permeance no greater than 2.0 perm/inch when tested
in accordance with ASTM-E-96-90. 3. Concrete slab perimeter insulation
must be protected from physical damage and ultra violet light
deterioration.
SECTION 305.11 Ducts and Fans.
305.11.1 Air handling duct systems
shall be installed and sealed to meet the requirement of UMC Sections
604. Portions conveying conditioned air shall either be insulated
to a minimum installed level of R-4.2 (or any higher level required
by UMC Section 604) or be enclosed entirely in conditioned space.
Zone III shall be used for the purpose of this Section, unless
another Zone is approved by the Chief Building Official.
305.11.2 All duct insulation product
R-values shall be based on insulation only (excluding air films,
vapor barriers, or other duct components) and tested C-values
at 75?F mean temperature at the installed thickness, in accordance
with ASTM C518-85 or ASTM C177-85.
305.11.3 The installed thickness
of duct insulation used to determine its R-value shall be determined
as follows:
1. For duct board, duct liner
and factory-made rigid ducts not normally subjected to compression,
the nominal insulation thickness shall be used. 2. For duct wrap,
installed thickness shall be assumed to be 75 percent (25 percent
compression) of nominal thickness. 3. For factory-made flexible
air ducts, the installed thickness shall be determined by dividing
the difference between the actual outside diameter and nominal
inside diameter by 2.
305.11.4 Insulated flexible duct
products installed to meet this requirement must include labels,
in maximum intervals of 10 feet, showing the thermal performance
R-value for the duct insulation itself (excluding air films, vapor
barriers, or other duct components),based on the tests in Section
305.11.2 and the installed thickness determined by Section 305.11.3.3.
305.11.5 All fan systems, regardless
of volumetric capacity, that exhaust air from the building to
the outside shall be provided with backdraft or automatic dampers
to prevent air leakage.
305.11.6 All gravity ventilating
systems that serve conditioned space shall be provided with either
automatic or readily accessible, manually operated dampers in
all openings to the outside except combustion inlet and outlet
air openings and elevator shaft vents.
EXCEPTION: The requirements do
not apply to ducts and fans integral to combustion air ducts of
solid fuel burning devices or fireplaces.
SECTION 305.12 - Mandatory Requirements
for Outside Private Pool and Spa Heating Systems and Equipment.
305.12.1 Certification by Manufacturers.
Any pool or spa heating system or equipment may be installed only
if the manufacturer has certified that the system or equipment
has all of the following:
1. A readily accessible on-off
switch, mounted on the outside of the heater, that allows shutting
off the heater without adjusting the thermostat setting; and
2. No electric resistance heating;
and
EXCEPTIONS:
1. Pools or spas deriving at least
50% of the annual heating energy from on-site non-depletable sources.
Balance of energy use is not required to be taken from energy
budget surplus. 2. Listed package units with fully insulated enclosures,
and with tight-fitting covers that are insulated to at least R-12
up to a maximum size of 64 square feet.
3. No pilot light; and
4. High efficiency circulation
pump motors; and
5. Maximum capacity of heating
system, for pools installed for summer use only, derived from
depletable energy sources, = 405,000 BTU input. Pools intended
for year round use shall calculate their energy consumption at
332KBTU/yr/sq.ft at 100% equipment efficiency. Pools intended
for summer use only shall calculate their energy consumption at
29KBTU/yr/sq.ft at 100% equipment efficiency. Spas shall calculate
their energy consumption at 430KBTU/yr/sq.ft at 100% equipment
efficiency.
SECTION 305.13 - Natural and Liquid
Propane Gas Central Furnaces, Cooking Equipment, Private Pool
and Spa Heaters and Snowmelt:
305.12.2 Installation. Any pool
or spa heating system or equipment shall be installed with all
of the following:
1. At least 36" of pipe between
the filter and the heater, to allow for the future addition of
solar heating equipment; and 2. Directional inlets and time switches
for pools.
2.1 The pool shall have directional
inlets that adequately mix the pool water; and 2.2 The circulation
pump shall have a time switch that allows the pump to be set to
run in the off-peak electric demand period, and for the minimum
time necessary to maintain the water in the condition required
by applicable public health standards.
EXCEPTION: Where applicable public
health standards require on-peak operation.
2.3 Outdoor pools or spas with
a surface area> 800 ft2. shall not be heated.
EXCEPTION: Heating systems deriving
50% of energy from non-depletable sources, with a maximum area
of 1600 ft2.
305.13.1 Pilot Lights Prohibited.
Any natural or liquid propane gas system or equipment shall not
have a continuously burning pilot light:
EXCEPTIONS: Listed decorative
gas appliances
SECTION 305.14 - Mandatory Requirements
for Exterior Doors, Windows, and Fenestration Products.
305.14.1 Any manufactured doors
or windows or manufactured fenestration product may be installed
only if the manufacturer has certified to the Chief Building Official,
or if an independent certifying organization approved by the Chief
Building Official has certified, that the product complies with
all of the applicable requirements of this subsection.
305.14.1.1 Manufactured doors
and windows shall have air infiltration rates not exceeding those
shown in Table 3-3, when tested according to ASTM E283-91 at a
pressure differential of 75 pascals or 1.57 pounds/ft2.
305.14.1.2 Manufactured fenestration
products shall:
1. Be certified as to their overall
U-values as rated in accordance with the National Fenestration
Rating Council's NFRC-100-91 (June 28,1991), or in accordance
with "Table 5, Overall Coefficients of Heat Transmission
of Various Fenestration Products", as it appears on pages
27.6 and 27.7 of the ASHRAE 1993 Fundamentals Handbook, or in
accordance with a default table method approved by the Chief Building
Official; and 2. Have a temporary label, not to be removed before
inspection by the enforcement agency, listing the certified U-values;
and 3. Have a permanent label listing the U-value, certifying
organization, and rating procedures or a label to allow tracking
back to the original certification information on file with the
certifying organization.
Table 3-3
MAXIMUM AIR INFILTRATION RATES
Windows cfm/ft 2 of operable sash
crack TYPE RATE All 0.37 Residential Doors cfm/ft 2 of door area
swinging, sliding 0.37 All Other Doors cfm/ft 2 of door area sliding,
swinging (single door) 0.37 swinging (double door) 1.0
305.14.2 Site constructed doors,
skylights, and windows, including, but not limited to, field manufactured
doors, skylights, and windows, shall be caulked between the door,
skylights, or window and the building, and shall be weather-stripped.
EXCEPTION: Unframed glass doors
and fire doors.
SECTION 305.15 - Mandatory Requirements
for Joints and Other Openings. Joints and other openings in the
building envelope that are potential sources of air leakage shall
be caulked, gasketed, weather-stripped, or otherwise sealed to
limit infiltration and exfiltration.
SECTION 305.16 - Compliance Methods.
All residential buildings shall meet all of the following:
1. The mandatory requirements.
2. Either the performance standards or the prescriptive standards
or the requirements of the-Aspen Pitkin Green Program.
SECTION 306 - RESIDENTIAL PRESCRIPTIVE
COMPLIANCE
306.1 Buildings that are certified
to meet the requirements of the Aspen Pitkin Green Program or
receive an E-STAR TM rating of at least 80 points are exempt from
meeting the prescriptive requirements.
EXCEPTION: Buildings that contain
snowmelt, pool, or spa systems.
Any changes to the building design
will nullify the Aspen Pitkin Green Program exemption.
306.2 Buildings comply with the
prescriptive or tradeoff standards if they meet the requirements
of MEC CHECK, version 2.07. Chapter 2 of MEC CHECK is omitted
and replaced by the mandatory requirements of Section 305.
306.3 The prescriptive standards
do not allow the inclusion of snowmelt. (Snowmelt requires compliance
demonstration with the performance computer standard.)
306.4 The prescriptive standards
do not allow the inclusion of pool and spa energy use. (Pool and
spas require compliance demonstration with the performance computer
standard).
306.5 Heat transfers within the
same building to adjacent spaces that are not covered by the permit
and that are independently provided with space conditioning may
be considered to be zero. Heat transfers to spaces not yet provided
with space conditioning may be modeled as separate unconditioned
zones, or as outside conditions.
SECTION 307 - RESIDENTIAL PERFORMANCE
COMPLIANCE
307.1 Performance Standards. A building complies with the performance
standard if its combined calculated depletable energy use for
water heating (Section 307.1.1), space conditioning (Section 307.1.2),
snowmelt (Section 307.1.3), and pool and spa heating (Section
307.1.4), is less than or equal to the combined maximum allowable
energy use for both water heating, and space conditioning, even
if the building fails to meet either the water heating, or space
conditioning, budget alone.
EXCEPTION: Buildings that are
certified to meet the requirements of the Aspen Pitkin Green Program
and do not have snowmelt, swimming pool or spa heating system
equipment comply with the performance standard.
307.1.1 Water Heating Budgets.
The budgets for water heating systems are those calculated from
Equation 3-1.
Equation 3-1
ANNUAL WATER HEATING BUDGET (AWB):
For dwelling units less than 2500 ft 2:
AWB (kBtu/yr.-ft 2) = (14000)
+ 4.85 CFA
For dwelling units equal to or
greater than 2500 ft 2:
AWB (kBtu/yr.-ft 2) = (26125)
CFA
Where CFA the building's conditioned
floor area in square feet.
The annual water heating budget
calculated from Equation 3-1 may be met by either:
1. Calculating the energy consumption
of the proposed water heating system using an approved calculation
method or
2. Installing any gas storage
type non-re-circulating water heating system that does not exceed
50 gallons of capacity, meets the minimum standards specified
in the Appliance Efficiency Standards, and either has an R-12
external insulation wrap or has been determined by the Chief Building
Official to meet the annual water heating budget calculated from
Equation 3-1 without an external insulation wrap.
307.1.2 Space Conditioning Budget.
Space conditioning budgets shall be the calculated consumption
of energy from depletable sources required for space conditioning
in buildings in which the requirements for the prescriptive compliance
(Section 306) are installed. To determine the space-conditioning
budget, use an approved calculation method.
307.1.3 Snowmelt Energy Use (not
a budget) Snowmelt energy use shall be the consumption of snowmelt
system and equipment energy from depletable sources used for melting
snow. Snowmelt energy use for dwelling units is 34,42SBTU/yr/sq.ft.
at 100% equipment efficiency. Snowmelt energy use shall be added
to the subtotal source energy consumption calculated as per the
requirements of Section 307.2.2.2.
EXCEPTIONS:
1. Roof heating cable.
2. Areas critical to pedestrian
ingress, egress, or life safety may be snowmelted, with approval
from the Chief Building Official, on a case by case basis.
307.1.4 Pool and Spa Energy Use
(not a budget). Pool and spa energy use shall be the consumption
of energy from depletable sources used for heating pools and spas.
307.2 Compliance Demonstration
Requirements for Performance Standards. The application for a
building permit shall include documentation which demonstrates,
using an approved calculation method, the compliance version of
the City of Aspen/Pitkin County Energy Conservation Code's Public
Domain Computer Program or calculation method approved by the
Chief Building Official. All new buildings shall be designed so
that its total source energy consumption from depletable energy
sources does not exceed the combined water heating and space conditioning
budgets.
EXCEPTION:
1. Roof heating cable. 2. Areas
critical to pedestrian ingress, egress, or life safety may be
snowmelted, with approval from the Chief Building Official, on
a case by case basis.
307.2.1 To demonstrate compliance,
the applicant's documentation shall determine the combined energy
budget for the proposed building by adding the following:
1. The annual water heating budget
calculated from Equation 3-1 (kBtu/yr.-ft 2); and 2. The annual
space conditioning budget (kBtulyr.-ft 2) as determined pursuant
to Section 307.1.2.
307.2.2 Calculate the source energy
consumption subtotal of the proposed building, using the proposed
building's actual glazing area, orientation, and distribution,
and its actual energy conservation and other features, including
the actual water heating, space conditioning equipment and duct
conditions and locations. To determine the subtotal source energy
consumption, use an approved calculation method. Add snowmelt
energy use and pool and spa energy use to obtain total source
energy consumption.
Include in the calculation the
energy required for building cooling even if the building plans
do not indicate that air conditioning will be installed.
307.2.3 The proposed building
design complies if the total source energy consumption pursuant
to Section 307.2.2 is equal to or less than the combined energy
budget established in Section 307.2.1.
307.3 Required Calculation Assumptions.
The Chief Building Official shall publish the assumptions and
calculation methods it used to develop the standards for residential
buildings, including those specified in Section 307.
In determining the water heating
and space conditioning budgets and calculating the energy use
of the proposed building design, snowmelt energy use, and private
pool and private spa energy use, the applicant shall use only
these assumptions and calculation methods approved by the Chief
Building Official.
307.3.1 Such assumptions shall
include, but not be limited to, the following:
1. The operating conditions regarding
indoor temperature; occupancy loads and schedules; equipment loads
and operation schedules, including lighting, HVAC, and miscellaneous
electrical; and outdoor weather conditions;
2. The physical characteristics
of building pressurization, interior heat transfer, film coefficients,
shading coefficient and operation of installed shading devices,
ground temperatures, and the method of determining slab heat loss;
3. The applicable modeling procedures
for the assumptions, design conditions, and physical characteristics
described in Section 307.2.
EXCEPTION: The Chief Building
Official may approve alternative schedules, assumptions, and performance
modeling procedures that may be used in lieu of those described
in Section 307.3.1, provided such alternatives do not alter the
efficiency level required by these standards.
307.3.2 The total calculated annual
energy consumption shall include all energy used for comfort heating,
comfort cooling, ventilation for the health and comfort of occupants,
service water heating, snowmelt, and private pool and private
spa heating.
EXCEPTIONS:
1. Roof heating cable. 2. Areas
critical to pedestrian ingress, egress, or life safety may be
snowmelted, with approval from the Chief Building Official, on
a case by case basis.
307.3.3 Heat transfers within
the same building to adjacent spaces that are not covered by the
permit and that are independently provided with space conditioning
may be considered to be zero. Heat transfers to spaces not yet
provided with space conditioning may be modeled as separate unconditioned
zones, or as outside conditions.
307.3.4 The total calculated annual
energy consumption need not include energy from any non-depletable
sources, regardless of the purpose of the energy consumed.
307.3.5 The U-value of installed
manufactured fenestration products shall meet the requirements
of Section 305.14. The U-value of site-built fenestration products
shall be those published by the Chief Building Official, based
on an approved method that determines the area weighted average
U-value for generic types of products.
307.3.6 Shading coefficients for
interior devices used with fenestration products shall be taken
from Tables 25, 26, and 27 of Chapter 27 of the ASHRAE Handbook
of Fundamentals (1989), except that the minimum shading coefficient
that shall be assumed for any interior shading device is 0.66.
SECTION 308 - RESIDENTIAL ADDITIONS
308.1 Additions - Scope. Additions
to existing residential buildings shall meet the requirements
of Sections 303, 304, and 305; and, the requirements of this section
(308.2 or 308.3 below).
308.2 Prescriptive Approach. Additions
to existing buildings shall meet the requirements of either 1,
2, or 3 below, or Section 306.
1. Additions up to 50 square feet
shall not exceed 40 square feet of fenestration plus the fenestration
area that was removed by the addition, and the U-value shall not
exceed 0.40. 2. Additions greater than 50 square feet but less
than 150 square feet shall meet all the requirements of Section
306, except that the addition's total fenestration area limit
is the maximum of the chosen package plus the fenestration area
that was removed by the addition. 3. Additions greater than 150
square feet shall meet all the requirements of Section 306.
308.3 Performance Approach. Performance
calculations shall meet the requirements of either 1 or 2, below:
1. The addition complies if the
addition alone meets the combined water heating and space conditioning
energy budgets (see Section 307.2). 2. The addition complies if
the energy efficiency of the existing building is improved such
that the total source energy consumption of the improved existing
building and the addition is equal to or less than that of the
unimproved existing building.
SECTION 309 - RESIDENTIAL ALTERATIONS
309.1 Alterations -- Scope. Alterations
to existing residential buildings shall meet any requirements
of Sections 303, 304, and 305 that apply to the system or envelope
component being changed and the requirements of this section.
The U-value of any fenestration product replaced as part of an
alteration shall not exceed 0.40 as defined by the National Fenestration
Rating Council (i.e. whole product performance). An increase in
the area of fenestration or the installation of recessed cans
in a warm/cold ceiling is not an alteration and shall meet the
requirements of Section 306 or 307
NOTE: Fenestration products repaired
or replaced, not as part of an alteration, need not comply with
the U-value requirements applicable to alterations.
SECTION 310 - NONRESIDENTIAL BUILDINGS
Shall comply with the "Energy Guidelines for Commercial and
High-Rise Residential Buildings in Colorado or Colorado ComcheckEZ
1.2 and Section 303 of this code.
SECTION 311 - RESIDENTIAL SNOWMELT,
OUTSIDE POOL, OUTSIDE SPA SYSTEMS AND EQUIPMENT COMPLIANCE
311.1 Scope. Residential snowmelt,
outside pool, or outside spa systems and equipment may be installed
only if its calculated depletable energy use is allowed using
the method described in this section. This section applies to
all installations for which an application for a permit or renewal
of an existing permit is filed or is by law required to be filed
with or without an associated Building Permit. Residential snowmelt
or spa systems and equipment shall meet the requirements of Section
303 and 305.12.
311.2 Renewable Energy Mitigation
Program (REMP) Option -- Energy use for residential snowmelt systems,
outdoor spas, and outdoor pools may be supplemented as per the
following:
311.2.1. The REMP fee shall be
paid at the time of issuance of the building permit. Fees are
based on the amount of supplemental energy required above the
allowable energy budget (as per the performance method). All fees
collected pursuant to this section shall be recorded in a separate
fund by the City Finance Director and shall be spent in accordance
with a joint resolution by the Aspen City Council and Pitkin County
Board of County Commissioners.
311.2.2 This REMP option is voluntary.
Applicants interested in supplemental energy above the allowable
budget can alternatively choose to produce renewable energy on-
site with solar hot water, solar photovoltaics, or ground source
heat pumps. On-site renewable energy should offset at least 50%
of the supplemental energy needed, the balance shall come from
natural gas. Electric resistance heating is not permitted.
311.2.3 Snowmelt energy consumption
shall be calculated as in Section 307.1.3.
311.2.4 Outdoor pool and spas
shall have their energy consumption calculated as in Section 305.12
311.2.5 The REMP option for supplemental
energy is capped at 100,000,000 British Thermal Units (BTU) per
year or a total fee of $100,000, whichever is greater.
311.2.6 REMP fees for snowmelt,
spas, or pools shall be calculated according to the following
equation: [(Supplemental Energy in BTUs per year) 3412BTU/kWh]*20
years* $0.07/kWh
311.2.7 Residences using REMP
for supplemental energy must use the performance method see Sec
307. Minimum standards for the performance calculations are listed
in Section 305 under the mandatory requirements with the following
exceptions:
Wall Insulation R-22 Roof Insulation
R-38 Floor Insulation R-19 Boiler Efficiency 87% Fenestration
U=0.40
311.2.8 The following examples
are illustrated for residences using the REMP option for snowmelt,
spas, and/or pools. These residences that did not have BTU's available
from the performance method calculations and are using an 87%
efficient boiler.
Snowmelt Example (Snowmelt requested
500 sq. ft.)
(34,425(BTU per sq. ft. per year)
/.87 (efficiency rating of boiler))*500 (snowmelt area) = 19,784,482
(BTU/yr)/3412 (kWh per BTU) = 5798.5 (kWh/yr)* 20 (years)* .07/kWh
= $8,117.90
REMP fee will be $8,117.90
Pool Example (Pool summer use
only 600 sq. ft.)
(29000(BTU per sq. ft. per year)/.87
(efficiency rating of boiler))*600 (pool area) = 20,000,000 (BTU/yr)/3412
(kWh per BTU) = 5861.66 (kWh/yr)* 20(years)* .07/kWh = $8,206.00
REMP fee will be $8,206.00
Pool Example (Pool year around
outdoor use 600 sq. ft.)
(332000(BTU per sq. ft. per year)
/ .87 (efficiency rating of boiler))*600 (pool area) = 228,965,520
(BTU/yr) / 3412 (kWh per BTU) = 67,105.95 (kWh/yr)* 20 (years)*.07/kWh
= $93,948.00
REMP fee will be $93,948.00
Spa Example (Spa 100 sq. ft. year
around use)
(430000(BTU per sq. ft. per year)
/ .87 (efficiency rating of boiler))* 100 (spa area) = 49,425,287
(BTU/yr) / 3412 (kWh per BTU) = 14,485.72 (kWh/yr)* 20 (years)*
.07/kWh = $20,280.00
REMP fee will be $20,280.00
311.3 Renewable Energy Mitigation
Program (REMP) for houses over 5,000 sq. ft. A new home or remodel
over 5000 sq. ft. is required to offset a small portion of their
fossil fuel energy consumption through the use of on-site renewable
energy or through a flat fee payment to REMP.
311.3.1 This requirement applies
to all installations for which an application for a permit or
renewal of an existing permit is filed or is by law required to
be filed with or without an associated Building Permit.
311.3.2 The on-site renewable
energy requirement can be met by the installation of a two-kilowatt
photovoltaic or equivalent renewable energy system. This requirement
can be alternatively handled off-site by payment of a REMP fee
as follows:
over 5,000 sq. ft. $5,000.00 over
10,000 sq. ft. $10,000.00
SECTION 312 - RESIDENTIAL AND
NONRESIDENTIAL REPAIRS
312.1 Scope. Repairs to building
components, systems, or equipment which do not increase their
pre-existing energy consumption need not comply with the APECC.
If a building component, system, or piece of equipment is replaced,
however, it must be treated as an alteration. (Ord. No. 55-1999
§ 2 (part))
Copyright © ICLEI 1995 - 2005
|